Treatment method of ammonia refrigerant in refrigeration equipment

  【】When low-pressure equipment needs to be overhauled, the connection between the equipment and the refrigeration system must be cut off, a channel must be selected, the ammonia in the equipment must be sucked clean with the refrigeration compressor, and then the atmosphere can be connected to the equipment to repair the equipment. In the process of handling ammonia, it is necessary to be careful and repeated inspections to ensure safety in case of accidents.

  1. Treatment of low-pressure equipment

When the low-pressure equipment needs to be overhauled, the connection between the equipment and the refrigeration system must be cut off, a channel is selected, the ammonia in the equipment is sucked clean with the refrigeration compressor, and then the atmosphere is connected , The equipment can be repaired. In the process of handling ammonia, it is necessary to be careful and careful, and to check repeatedly to ensure safety in case of accidents.

   (1) Prepare all the tools needed for maintenance, and prepare safety protection facilities, such as gas masks, ventilators, rubber gloves, rubber hoses and first aid supplies.

   (2) Cut off the connection between the accident equipment and the refrigeration system, and put a ban on the closed valve.

   (3) Select an ammonia extraction line to drain the ammonia from the equipment to be repaired. For example, for the evaporator, the discharge pipeline of hot ammonia defrost should be selected to pump the ammonia to the discharge barrel or the circulation barrel.

After the valve of   (4) system pipeline is adjusted correctly, the selected ammonia pipeline can be used to turn on the compressor for evacuation. When the low pressure pressure drops below 0MPa, stop the machine, and restart the evacuation after the pressure rises. This is repeated 2-3 times, and the pressure rises slightly and is below 0MPa, indicating that the equipment has been evacuated.

  (5) If the ammonia in some equipment is not easy to drain, you can vent it through a vent valve or use a rubber tube to put the ammonia into the condenser pool or outdoor bucket.

  (6) After the equipment to be overhauled is evacuated, the atmosphere should be connected to it to let the ammonia gas escape and reduce the concentration. Repair the equipment can only be carried out after everything is correct.

  2. Treatment method of high-pressure equipment

The treatment of ammonia during the maintenance of high-pressure equipment should be considered in terms of safety. Ammonia can be sent to the low-pressure equipment through a connecting pipeline, for example, through a drain pipe, an oil collector, and then a reduction The pressure pipe sends the ammonia to the drain tank or low-pressure circulation tank for storage.

  After the ammonia in the high-pressure equipment is discharged into the low-pressure equipment, the remaining ammonia can pass through the oil drain line and the drain valve of the oil collector, and then through the rubber tube, into the condenser pool or Inside the sewer.

Hangzhou E cool refrigeration Co.,Ltd has created its reputation on a commitment to manufacturing high-quality products and services while satisfy the needs of customers.

If you are looking for start capacitor suppliers air conditioner capacitor, we have plenty of them in our store. We have start capacitor suppliers and many others. Visit Arkool Refrigeration to know more.

With a complete manufacturing plant, Hangzhou E cool refrigeration Co.,Ltd is able to meet the most stringent specifications, no matter the type of product. A dedicated team of experts handle these value-added services, ensuring that customer needs are met on time, consistently monitoring quality and performance of refrigerant gas to the highest international standards. Visit Arkool Refrigeration to learn more.

GET IN TOUCH WITH Us
recommended articles
knowledge NEWS CENTER NEWS
With the signing of the Montreal Agreement in 1987, CFC refrigerants (such as R-11, R-12, etc.) have been completely banned due to their strong damaging effects on atmospheric ozone.
  Refrigeration network: The design of each air conditioner has the problem of how to determine the refrigerant charge, especially in the air conditioner that uses capillary tubes as throttling devices, because the capillary tubes have a higher regulating capacity The expansion valve is poor, and the change of the charge has a greater impact on its performance.
  【】Refrigerants are also called refrigeration working fluids, commonly known as refrigerants in some areas in the south.
As we all know, the power density of equipment in the computer room is high, so the volume heat is high.
  The air source heat pump is in winter heating conditions.
  【】Semiconductor cooling fins, also called thermoelectric cooling fins, are cooling devices composed of semiconductors.
   R22 and R410, which are commonly used in air conditioning and refrigeration, are two different refrigerants.
  【】In practical applications, some of the following methods are often used to detect whether the refrigerant in the refrigeration system is sufficient.
no data
 12-1501 Yangguangcheng, Lvting Road, Yuhang District, Hangzhou, Zhejiang Province, China
Icetop refrigeration
Mobile: +86 18668096671
E-Mail: ecm@ecmrefrigerant.com
Whatsapp/Wechat:
+8618668096671
Wechat: +8618668096671
QQ: 435672887
Mobile: +8613429676071
E-Mail: cool@ecmrefrigerant.com
Whatsapp/Wechat:
+8613429676071
no data
Copyright © 2025 Hangzhou Icetop refrigeration Co.,Ltd  /  Oasis Chemical Co.,Limited / A-COOL MANUFACTURING CO.,LIMITED  | Sitemap
Customer service
detect