Refrigerant recovery method of industrial chiller

  【】In the repair or maintenance process of industrial chillers, it is necessary to recover the refrigerant to facilitate subsequent maintenance work. There are two common refrigerant recovery methods in industrial chillers: one is to recover the refrigerant to the accumulator, and the other is to recover the refrigerant to the refrigerant cylinder.

   1. How to recover the refrigerant from the industrial chiller to the accumulator?

   Note: Our industrial chillers are equipped with high/low pressure pressure controllers. When recovering refrigerant, the contacts of the high/low pressure pressure controller should be kept normally closed to avoid recycling refrigeration The machine shuts down due to pressure during the treatment.

   The specific steps for recovering the refrigerant from the industrial chiller to the accumulator are as follows: 1. Open all the valves of the refrigeration system of the industrial chiller, and turn the suction stop valve counterclockwise to make it full Open state, and then use the multi-purpose connector to connect the repair valve with the suction shut-off valve. 2. Close the repair valve and adjust the suction shut-off valve to the three-way position; 3. Turn clockwise to close the outlet shut-off valve of the accumulator; 4. Start the refrigeration compressor of the industrial chiller, the main force in the evaporator It is sucked into the condenser and accumulator.

   2. How to recover the refrigerant from the industrial chiller to the cylinder?

  The refrigerant is stored in a special steel cylinder. When the refrigerant in the industrial water cooler is recovered to the cylinder:

  1, it should be in the bypass hole channel of the suction stop valve first Connect the repair valve with a pressure vacuum gauge, and adjust the suction stop valve to the three-way position.

  2, turn the exhaust shut-off valve counterclockwise to the fully open state, unscrew the plug of the bypass hole of the exhaust shut-off valve, and install the multi-purpose connector.

  3. Use a hose to connect the empty refrigerant cylinder to the multi-purpose joint of the exhaust shut-off valve, but do not tighten the joint at the end of the refrigerant cylinder.

  4. Slightly open the exhaust shut-off valve to remove the air in the connecting hose, and then tighten the joint.

  5. Fully open the valve of the refrigerant cylinder, and use cooling water to continuously shower the refrigerant cylinder.

  6. Pneumatic compressor, slowly close the exhaust shut-off valve clockwise, and the refrigerant in the industrial chiller is gradually compressed into the refrigerant cylinder.

No matter whether the refrigerant of the industrial chiller is recovered to the accumulator or the steel cylinder, as long as the refrigerant recovery is completed, the pressure of the pressure gauge at the suction end is 0.01MPa. After the compressor is turned off, if If the pressure does not rise, it means that the refrigerant has been recovered. If the pressure has risen, it means that the refrigerant has not been recovered, and the operation should be performed again according to the above method.

Hangzhou E cool refrigeration Co.,Ltd works very hard to understand your objectives, then create a program that can help you meet them.

Hangzhou E cool refrigeration Co.,Ltd’s mission is to provide high quality care and services to our members and to be profitable in the process.

The proprietor has many years experience in providing promotion services and is a sought after expert in air conditioner capacitor.

refrigerant gas provider at Arkool Refrigeration offers a wide variety of in many options. quality is absolutely ensured if you choose us. welcome to visit our factory.

Using high-quality materials to produce air conditioner capacitor is one of the most important part during manufacturing.

GET IN TOUCH WITH Us
recommended articles
knowledge NEWS CENTER NEWS
With the signing of the Montreal Agreement in 1987, CFC refrigerants (such as R-11, R-12, etc.) have been completely banned due to their strong damaging effects on atmospheric ozone.
  Refrigeration network: The design of each air conditioner has the problem of how to determine the refrigerant charge, especially in the air conditioner that uses capillary tubes as throttling devices, because the capillary tubes have a higher regulating capacity The expansion valve is poor, and the change of the charge has a greater impact on its performance.
  【】Refrigerants are also called refrigeration working fluids, commonly known as refrigerants in some areas in the south.
As we all know, the power density of equipment in the computer room is high, so the volume heat is high.
  The air source heat pump is in winter heating conditions.
  【】Semiconductor cooling fins, also called thermoelectric cooling fins, are cooling devices composed of semiconductors.
   R22 and R410, which are commonly used in air conditioning and refrigeration, are two different refrigerants.
  【】In practical applications, some of the following methods are often used to detect whether the refrigerant in the refrigeration system is sufficient.
no data
 12-1501 Yangguangcheng, Lvting Road, Yuhang District, Hangzhou, Zhejiang Province, China
Icetop refrigeration
Mobile: +86 18668096671
E-Mail: ecm@ecmrefrigerant.com
Whatsapp/Wechat:
+8618668096671
Wechat: +8618668096671
QQ: 435672887
Mobile: +8613429676071
E-Mail: cool@ecmrefrigerant.com
Whatsapp/Wechat:
+8613429676071
no data
Copyright © 2025 Hangzhou Icetop refrigeration Co.,Ltd  /  Oasis Chemical Co.,Limited / A-COOL MANUFACTURING CO.,LIMITED  | Sitemap
Customer service
detect