R404 refrigerant R22 refrigerant instead

1。 Using r404a replace R22 lubricating oil is the most major problem, must be used PVE ester oil to replace R22 with mineral oil. Ester lubricant and high affinity for water and water is poor, it should be used in the try to avoid contact with outside air, container after opening, should use as soon as possible, after use shall be kept sealed; Away from the oxidant, strong alkali, strong acid, save in ventilated place; When using, should avoid contact with skin and eyes, avoid inhaling its steam and spray.

2。 The exhaust pressure of refrigerant R404A is about 1 of R22. 2 times, mass flow rate is 1 of R22. About five times, exhaust velocity increases, the resistance increased. Condenser, in general, the change of heat capacity than R22 increased 20% ~ 30%.

3。 Same temperature R404A and R22 saturation pressure is different, so the R404A institution and R22 different thermodynamic expansion valve movement. Because R404A cooling agent and lubricant intermiscibility of sealing material is different, expansion valve sealing material also should accordingly change, therefore, on the choice of thermal expansion valve should choose R404A dedicated expansion valve.

4。 Due to the saturation pressure is higher than R22 R404A, so the system pressure container design pressure to make changes, to ensure safety. Such as accumulator and gas-liquid separator, etc. At the same time, system parts are installed on the relief valve and fusible plug value will change accordingly. Because in the same conditions of displacement, R404A gas density around 50% larger than that of R22, so when using R404A refrigerant piping design, selection of pipe diameter than the R22.

5。 The same compressor, using R404A current than R22, so the compressor ac contactor, thermal relay, and the wire diameter of the cable to adjust. In the aspect of system protection, high pressure switch Settings from 2. 45 mpa is adjusted for 2. 7MPa。

6。 Because of 404 a saturation pressure and R22 is different, so the air tightness test pressure than R22. System at the same time the vacuum degree should be higher than that of R22, moisture content is lower than R22. To with liquid refrigerant filling type filling, in case of R404A configuration changes.

7。 R404A are azeotropic mixed working medium, non azeotropic mixture composition concentration changes with the temperature, pressure, the production of refrigeration system, debugging and maintenance has brought certain difficulties, the heat transfer performance of the system is also can produce certain effect, especially when the refrigerant leakage, all system refrigerant needs emptying displacement, so as to guarantee the proportion of each blend components, and to achieve design refrigeration effect, otherwise it will get worse and worse. Because of refrigerant R404A and lubricating oil has nothing to do with the intermiscibility of water is very good, so the system of water and residue, cleanliness requirements such as compared with R22 refrigerant are improved, R404A moisture control and impurities control system is a more important indicator, corresponding filter unit in the system, etc. To make changes.

4。 Due to the saturation pressure is higher than R22 R404A, so the system pressure container design pressure to make changes, to ensure safety. Such as accumulator and gas-liquid separator, etc. At the same time, system parts are installed on the relief valve and fusible plug value will change accordingly. Because in the same conditions of displacement, R404A gas density around 50% larger than that of R22, so when using R404A refrigerant piping design, selection of pipe diameter than the R22.

5。 The same compressor, using R404A current than R22, so the compressor ac contactor, thermal relay, and the wire diameter of the cable to adjust. In the aspect of system protection, high pressure switch Settings from 2. 45 mpa is adjusted for 2. 7MPa。

6。 Because of 404 a saturation pressure and R22 is different, so the air tightness test pressure than R22. System at the same time the vacuum degree should be higher than that of R22, moisture content is lower than R22. To with liquid refrigerant filling type filling, in case of R404A configuration changes.

7。 R404A are azeotropic mixed working medium, non azeotropic mixture composition concentration changes with the temperature, pressure, the production of refrigeration system, debugging and maintenance has brought certain difficulties, the heat transfer performance of the system is also can produce certain effect, especially when the refrigerant leakage, all system refrigerant needs emptying displacement, so as to guarantee the proportion of each blend components, and to achieve design refrigeration effect, otherwise it will get worse and worse. Because of refrigerant R404A and lubricating oil has nothing to do with the intermiscibility of water is very good, so the system of water and residue, cleanliness requirements such as compared with R22 refrigerant are improved, R404A moisture control and impurities control system is a more important indicator, corresponding filter unit in the system, etc. To make changes.

Maintaining start capacitor suppliers is not as easy as it may seem. You have to do plenty of important tasks. So cruel is the truth unless you've got a to help you.

Review Hangzhou E cool refrigeration Co.,Ltd's progress at regular intervals, so we can continue with the strategies that work well and change or eliminate the ones that don't give the results we are looking for.

Hangzhou E cool refrigeration Co.,Ltd has been focusing on reaching the ideal profits.

Basically, you cannot have a start capacitor suppliers without having the right air conditioner capacitor. Since you are going to use it regularly, be sure to invest in one that has a high quality.

With its quality certified and recognised by professional intitutions and customers, Hangzhou E cool refrigeration Co.,Ltd is one of the leading providers in China.

GET IN TOUCH WITH Us
recommended articles
knowledge NEWS CENTER NEWS
With the signing of the Montreal Agreement in 1987, CFC refrigerants (such as R-11, R-12, etc.) have been completely banned due to their strong damaging effects on atmospheric ozone.
  Refrigeration network: The design of each air conditioner has the problem of how to determine the refrigerant charge, especially in the air conditioner that uses capillary tubes as throttling devices, because the capillary tubes have a higher regulating capacity The expansion valve is poor, and the change of the charge has a greater impact on its performance.
  【】Refrigerants are also called refrigeration working fluids, commonly known as refrigerants in some areas in the south.
As we all know, the power density of equipment in the computer room is high, so the volume heat is high.
  The air source heat pump is in winter heating conditions.
  【】Semiconductor cooling fins, also called thermoelectric cooling fins, are cooling devices composed of semiconductors.
   R22 and R410, which are commonly used in air conditioning and refrigeration, are two different refrigerants.
  【】In practical applications, some of the following methods are often used to detect whether the refrigerant in the refrigeration system is sufficient.
no data
 12-1501 Yangguangcheng, Lvting Road, Yuhang District, Hangzhou, Zhejiang Province, China
Icetop refrigeration
Mobile: +86 18668096671
E-Mail: ecm@ecmrefrigerant.com
Whatsapp/Wechat:
+8618668096671
Wechat: +8618668096671
QQ: 435672887
Mobile: +8613429676071
E-Mail: cool@ecmrefrigerant.com
Whatsapp/Wechat:
+8613429676071
no data
Copyright © 2025 Hangzhou Icetop refrigeration Co.,Ltd  /  Oasis Chemical Co.,Limited / A-COOL MANUFACTURING CO.,LIMITED  | Sitemap
Customer service
detect