【】1. How to recover the refrigerant from the industrial chiller to the accumulator?
The specific steps for recovering the refrigerant from the industrial chiller to the accumulator are:
1. Open all the valves of the industrial chiller refrigeration system, and turn the suction shut-off valve counterclockwise to make it fully open, and then connect the repair valve to the suction shut-off valve with a multi-purpose connector;
2, close the repair valve, and adjust the suction shut-off valve to the three-way position;
3, turn clockwise to close the outlet shut-off valve of the reservoir;
4. Start the refrigeration compressor of the industrial chiller, and the main force in the evaporator is sucked into the condenser and accumulator.
Second, how to recover the refrigerant from the industrial water chiller to the cylinder?
The refrigerant is stored in a special steel cylinder, and the steps to recover the refrigerant from the industrial water chiller to the cylinder :
1. Connect the repair valve with a pressure vacuum gauge to the bypass hole of the suction shut-off valve first, and adjust the suction shut-off valve to the three-way position.
2, turn the exhaust shut-off valve counterclockwise to the fully open state, unscrew the plug of the bypass hole of the exhaust shut-off valve, and install the multi-purpose connector.
3. Use a hose to connect the empty refrigerant cylinder to the multi-purpose joint of the exhaust shut-off valve, but do not tighten the joint at the end of the refrigerant cylinder.
4. Slightly open the exhaust shut-off valve to remove the air in the connecting hose, and then tighten the joint.
5. Fully open the valve of the refrigerant cylinder, and use cooling water to continuously shower the refrigerant cylinder.
6. Pneumatic compressor, slowly close the exhaust shut-off valve clockwise, and the refrigerant in the industrial chiller is gradually compressed into the refrigerant cylinder.
No matter whether the refrigerant of the industrial chiller is recovered to the accumulator or the steel cylinder, as long as the refrigerant recovery is completed, the pressure of the pressure gauge at the suction end is 0.01MPa. After the compressor is turned off, if If the pressure does not rise, it means that the refrigerant has been recovered. If the pressure has risen, it means that the refrigerant has not been recovered, and the operation should be performed again according to the above method.
Getting doesn't have to be expensive, time-consuming, or difficult. It all comes down to the right method and a start capacitor suppliers refrigerant gas in place.
Hangzhou E cool refrigeration Co.,Ltd aligns itself with customers as partners to assist them in achieving their goals and objectives.
start capacitor suppliers air conditioner capacitor is slower than start capacitor suppliers but has a number of special applications, such as for start capacitor suppliers.
The best way of start capacitor suppliers is to get a start capacitor suppliers refrigerant gas.
This is especially true when Hangzhou E cool refrigeration Co.,Ltd have got a global business that's building bridges between manufacturers and customers across the globe.