loading

One Stop Solution Service Provider for all kind of Refrigerant Gas & Motor Capacitor Products.

What kind of equipment does the high and low pressure refrigerant charge method apply to?

by:Arkool     2021-05-26

  【】There are generally two types of refrigerant charging methods: low-pressure charging and high-pressure charging. The advantage of the low pressure charging method is that it is easier to control the amount of refrigerant charged, safe and not easy to damage the components, but the charging time is longer, and the refrigerant is in a gaseous state and has a large water content, which must be processed by a dryer. The advantage of the high-pressure charging method is that the charging time is short, but it is difficult to control the refrigerant charge, especially for small equipment, so it is suitable for refrigeration equipment with a large refrigerant charge.

   At present, small and medium air conditioners and other refrigeration equipment often use low-pressure gas refrigerant charging methods during maintenance.

  ①Put the refrigerant cylinder on the scale and screw on the cylinder connector.

  ②Tighten the compressor low-pressure suction control valve clockwise, close the multi-channel port, and then unscrew the screw plugs and other connecting parts on the multi-channel port.

  ③ Install a three-way reversing valve, one end is connected to a vacuum pressure gauge, the other end is connected to a copper pipe with a diameter of 6mm, and connected to the joint of the refrigerant cylinder through a filter drier.

  ④ Slightly open the valve on the cylinder to fill the copper pipe with Freon gas, then slightly open the joint nut on the three-way reversing valve connector, and use the pressure of the Freon gas to fill the tube and dry filter The air in the container is exhausted, and then all the joint nuts are tightened to open the cylinder valve.

  ⑤ Make the connecting pipe and the filter drier in a state of being unstressed, read the weight of the cylinder from the scale, and pay attention to the filling equipment and the scale not to bear external force, so as not to affect the reading.

  ⑥ Rotate the compressor's low-pressure suction control valve clockwise to make the multi-purpose channel port and the low-pressure suction pipe and the compressor in a communication state, and the refrigerant enters the refrigeration system. When charging, pay attention to the change of the weight of the refrigerant cylinder and the change of the pressure of the low pressure gauge (generally no more than 98 ~ 196kPa). If the pressure has reached equilibrium and the charging volume has not reached the specified value, the cooling water (or cooling fan) should be turned on first, and the compressor should be started for charging after the cooling water flows out of the condenser water outlet. Before starting the machine, the low-pressure suction control valve should be rotated clockwise, and the multi-purpose channel port should be closed to avoid liquid shock (if there is liquid shock, stop immediately), and then slowly open the mostly-used channel port clockwise to make the refrigerant Enter the refrigeration system.

  ⑦When the specified filling volume is reached, first close the cylinder valve, then turn the low-pressure suction control valve counterclockwise, close the multi-purpose channel port, and then immediately stop the compressor.

  ⑧ Remove the connecting nut, the filling appliance and the three-way reversing valve, and install and tighten the fine-tooth joint, low-pressure meter and other components that were previously removed.

  ⑨ turn the low-pressure suction valve clockwise 1/2 ~ 3/4 turn to make the multi-purpose channel port communicate with the low-pressure gauge and the pressure controller (the opening size is subject to the low-pressure gauge pointer without beating).


Hangzhou E cool refrigeration Co.,Ltd has various branches in local businesses, servicing customers and helping to pull in traffic to those businesses.
Hangzhou E cool refrigeration Co.,Ltd are a market-focused, process-centered organization that develops and delivers innovative solutions to our customers, consistently outperforms our peers, produces predictable earnings for our customers, and provides a dynamic and challenging environment for our employees.
As the manufacturing procedure of air conditioner capacitor becomes more regulated, the costs to businesses will increase and the workforce will suffer as a result.
Our company specializes in selling refrigerant gas as well as providing relevant services.
Our commitment to equal employment and diversity is a global one as we serve customers and employ people around the world. Hangzhou E cool refrigeration Co.,Ltd finds it as a business imperative that is essential to thriving in a competitive global marketplace.
Custom message
Chat Online 编辑模式下无法使用
Chat Online inputting...