Common refrigerant charging methods for central air-conditioning

by:Arkool     2021-05-29

  【】In practical applications, some of the following methods are often used to detect whether the refrigerant in the refrigeration system is sufficient. Let’s analyze the drawbacks of these charging methods:

  1. Touch the air by hand Pipe and exhaust pipe sense the cold and heat of the copper pipe;

  2, observe the bubbles in the sight glass;

  3, measure the high and low pressure;

  4 Measure the compressor current;

  5, calculate the degree of superheat;

  6, observe the condensation on the suction pipe;

  7, weigh the weight Note.

  1. Touch the suction pipe and exhaust pipe to sense the heat and cold of the copper pipe

   Everyone has different feelings of cold and heat. If your hands have calluses, then you perceive The temperature is higher than actual. Normally the human body feels hot to temperatures above 37°C and cold to temperatures below 37°C. The temperature limit of skin perception is 49℃, so the liquid pipe temperature perceived by your hand is not necessarily a good condensing temperature.

  2. Observe the bubbles in the sight glass

   This does show that there are bubbles that indicate the lack of refrigerant, but the pressure loss of the liquid pipe can also cause bubbles. If the pressure loss of the liquid pipe is large, the liquid refrigerant will flash into a gas, and the flash gas will reduce the flow of the refrigerant when flowing through the expansion valve and will also corrode the expansion valve. If the subcooling of the system is small, the pressure loss can easily produce bubbles seen in the sight glass.

   If you see that the bubbles in the sight glass are caused by pressure loss rather than insufficient refrigerant, then you continue to add refrigerant to eliminate the bubbles, you will find that the high pressure rises and causes a jump machine. This method cannot correctly judge the refrigerant charge of the system.

  3. Measuring high and low pressures

   This method is used more, but it should be noted that the condensing air volume and the evaporating air volume are not satisfied, which will affect the refrigerant pressure tested. If the condensing air volume is insufficient, the high pressure will be very high, and if the evaporating air volume of the expansion valve system is insufficient, the low pressure will be very low. Before you test the system pressure, you must confirm that the condensing air volume and evaporating air volume are sufficient. The fin coil and filter should be clean, and the fan speed should be correct; check that the fan blades are not deformed or damaged, and are correctly installed on the shaft.

  4. Measuring compressor current

   This method is used more, but it should be noted that the current tested under different conditions is also different, for example, the current is subject to the voltage of the main power supply. The deviation of the voltage value causes the deviation of the current.

  5. Calculate the degree of superheat

   calculate the degree of superheat by measuring the suction temperature and pressure value of the suction pipe on the evaporator, the pressure value is converted into a temperature value minus the suction temperature The difference between the values u200bu200bis the degree of superheat.

   But it should be noted that if the system is flushed to ensure the correct degree of superheat in a cold day, the system will experience excessive refrigerant in a hot day. For the expansion valve system, it is easy to overcharge. Because the expansion valve will automatically open and close, the excessive or insufficient refrigerant flow through the coil will maintain the same superheat. If you recognize this, it will cause condensation More refrigerant accumulates in the device, causing high pressure rise, high current, and compressor loss.

  6. Observe the condensation on the suction pipe

   When the capillary system is flushing refrigerant, it will observe the condensation on the suction pipe. This injection method depends on The flow rate of the refrigerant liquid in the capillary tube and the pressure difference between the two ends. The heat transfer effect of the evaporator can be fully exerted only when the capillary tube is operated under the design conditions. If the air volume of the evaporator is normal, it is found that the refrigerant flows through the evaporator according to the load change, preventing the formation of the frost tube. If the load is reduced, the liquid refrigerant will flow through the evaporator, and when it enters the suction pipe, the water vapor in the surrounding air will condense on the copper pipe. If there is enough liquid refrigerant, tube exposure will occur.

   But note that when this method is used in a thermal expansion valve system, it will be found that the production of the exposed tube does not indicate the amount of refrigerant injected (even if an excessive amount of refrigerant is injected), because the expansion valve The temperature will be adjusted automatically.

  7. Weighing and filling (this is the best method)

   Actually, the weighing and filling method is the best method among the above methods. It is suitable for Any refrigeration system. The method is to weigh the refrigerant charged. As long as the manufacturer indicates the correct filling amount of the water-cooled cabinet or split machine on the nameplate. This method is the approved recommended filling method.

   Note: When starting the equipment after a power failure for more than 12 hours, the crankcase heater must be energized and preheated first. The purpose is to evaporate the liquid refrigerant mixed in the refrigerant oil in the crankcase to avoid the compressor Liquid refrigerant is sucked in, causing liquid compression.


Hangzhou E cool refrigeration Co.,Ltd thinks that effective market design can improve liquidity, efficiency, and equity in markets.
Hangzhou E cool refrigeration Co.,Ltd are a market-focused, process-centered organization that develops and delivers innovative solutions to our customers, consistently outperforms our peers, produces predictable earnings for our customers, and provides a dynamic and challenging environment for our employees.
The risk of start capacitor suppliers is reduced by start capacitor suppliers with the consumption of .
Equipping refrigerant gas with innovative technology and updated processes will simplify daily compliance duties so that they can focus on attracting, retaining, and developing the most engaged workforce possible.
So, what's a manufacturer to do? Familiarize ourselves with producing air conditioner capacitor in various technologies.
Custom message
Chat Online 编辑模式下无法使用
Chat Online inputting...